Product Features
Core structure
Fan: low-noise centrifugal fan, equipped with capacitor motor, supports three-speed regulation.
Coil: The copper tube and aluminum fins form a heat exchanger, with the outer diameter of the copper tube of 10-16mm and the spacing between the fins of 2-3mm. The heat exchange efficiency is improved through optimized design.
Shell: galvanized steel plate or aluminum alloy material, corrosion-resistant and high strength, condensate pan adopts integrated molding process, no weld, good leakage resistance.
Control system: adjust the opening and closing of the electric valve and the speed of the fan through the thermostat, and control the water flow or air volume to achieve constant temperature.
Working principle
The unit forcibly circulates indoor air through the fan to make it flow over the surface of the coil. The cold/hot water flowing in the coil exchanges heat with the air, and then the air is cooled or heated and sent back to the room. Fresh air is supplemented after being treated by an independent fresh air system to ensure indoor air quality.
Product advantages and Application scenarios
Product advantage
Concealed and beautiful: embedded in the ceiling, integrated with interior decoration, saving space and not affecting visual effects.
Low-noise operation: Low-noise fan and optimized air duct design are adopted, and the operation noise is as low as 40-50dB(A), which is suitable for the environment with high mute demand.
Energy saving and high efficiency: equipped with efficient heat exchanger and frequency conversion technology, the output of cold and heat can be adjusted to reduce energy consumption; Some models support four-pipe system, which can provide cooling/heating at the same time.
Uniform air supply: the design of three-dimensional spiral blades ensures uniform air distribution and avoids local temperature difference.Convenient maintenance: modular design and reserved access port are convenient for cleaning the filter screen and maintaining the fan and coil.
Flexible installation: the compact fuselage adapts to a variety of building structures, and the pipeline connection is simple, and the installation can be completed by one person.
Application scenarios
Commercial places: hotel rooms, shopping malls, office buildings, to meet the temperature control needs of independent spaces.
Medical environment: the hospital ward provides a clean and temperature-controlled rehabilitation environment.
Living space: family bedroom, villa, to achieve personalized temperature control and maintain indoor beauty.
Public facilities: exhibition hall, school, to meet the needs of large space air conditioning.
Equipment Maintenance and Care
Regularly clean the filter and condenser to maintain airflow efficiency.
Regularly check the motor for safe and smooth operation.
Fan Coil Unit(3row) | |||||||||||
Model number/ property | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-119 | FP-136 | FP-170 | FP-204 | FP-238 | |
Air Flow (m³/h) | Top grade | 340 | 510 | 680 | 850 | 1020 | 1190 | 1360 | 1700 | 2040 | 2380 |
Mid-range | 255 | 383 | 510 | 638 | 765 | 893 | 1020 | 1275 | 1530 | 1785 | |
Low-end | 170 | 255 | 340 | 425 | 510 | 595 | 680 | 850 | 1020 | 1190 | |
Cooling(W) | Top grade | 1800 | 2700 | 3600 | 4500 | 5400 | 6300 | 7200 | 9000 | 10800 | 12600 |
Mid-range | 1440 | 2160 | 2880 | 3600 | 4320 | 5040 | 5760 | 7200 | 8640 | 10080 | |
Low-end | 1170 | 1755 | 2340 | 2925 | 3510 | 4095 | 4680 | 5850 | 7020 | 8190 | |
Energy efficieng coefficient of cooling (FCEER) W/W | 12Pa | 46 | 49 | 54 | 54 | 51 | 49 | 49 | 53 | 51 | 48 |
30Pa | 39 | 43 | 47 | 49 | 45 | 46 | 43 | 47 | 46 | 44 | |
50Pa | 35 | 39 | 41 | 43 | 42 | 43 | 38 | 40 | 40 | 38 | |
Heat supply(W) Water supply temperature 60℃ | Top grade | 2700 | 4050 | 5400 | 6750 | 8100 | 9450 | 10800 | 13500 | 16200 | 18900 |
Mid-range | 2160 | 3240 | 4320 | 5400 | 6480 | 7560 | 8640 | 10800 | 12960 | 15120 | |
Low-end | 1755 | 2633 | 3510 | 4388 | 5265 | 6143 | 7020 | 8775 | 10530 | 12285 | |
Energy efficieng coefficient of heatig (FCCOP) W/W Water supply temperature 60℃ | 12Pa | 68 | 73 | 81 | 82 | 76 | 74 | 73 | 79 | 77 | 72 |
30Pa | 58 | 65 | 70 | 73 | 68 | 69 | 64 | 70 | 69 | 66 | |
50Pa | 53 | 59 | 61 | 64 | 63 | 64 | 58 | 60 | 60 | 57 | |
Heat supply (W) Water supply temperature 45℃ | Top grade | 1800 | 2700 | 3600 | 4500 | 5400 | 6300 | 7200 | 9000 | 10800 | 12600 |
Mid-range | 1440 | 2160 | 2880 | 3600 | 4320 | 5040 | 5760 | 7200 | 8640 | 10080 | |
Low-end | 1170 | 1755 | 2340 | 2925 | 3510 | 4095 | 4680 | 5850 | 7020 | 8190 | |
Energy efficieng coefficient of heatig (FCCOP) W/W Water supply temperature 45℃ | 12Pa | 46 | 49 | 54 | 54 | 51 | 49 | 49 | 53 | 51 | 48 |
30Pa | 39 | 43 | 47 | 49 | 45 | 46 | 43 | 47 | 46 | 44 | |
50Pa | 35 | 39 | 41 | 43 | 42 | 43 | 38 | 40 | 40 | 38 | |
Input power(W) | 12Pa | 36 | 50 | 60 | 74 | 93 | 112 | 130 | 147 | 183 | 221 |
30Pa | 43 | 57 | 70 | 84 | 105 | 121 | 151 | 169 | 206 | 245 | |
50Pa | 48 | 64 | 81 | 97 | 114 | 131 | 169 | 204 | 243 | 291 | |
Noise dB(A) | 12Pa | 37 | 39 | 41 | 43 | 45 | 46 | 46 | 48 | 50 | 52 |
30Pa | 40 | 42 | 44 | 46 | 47 | 48 | 48 | 50 | 52 | 54 | |
50Pa | 42 | 44 | 46 | 47 | 49 | 50 | 50 | 52 | 54 | 56 | |
Air blower | Form | Forward multi-wing centrifugal double suction fan | |||||||||
Quantity | 1 | 2 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | |
Electric machine | Form | Capacitor running asynchronous motor(220V/50Hz,protection class IP20,insulation class B) | |||||||||
Quantity | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | |||
Heat exchanger | Structuralform | Copper tube string aluminum sheet,mechanical expansion | |||||||||
Inlet and outet diameter | RC3/4(Conical internal thread) | ||||||||||
Other | Design pressure 1.6MPa,test pressure 2.5MPa | ||||||||||
Cold water quantity (T/h) | 0.39 | 0.55 | 0.7 | 0.82 | 0.91 | 1.21 | 1.34 | 1.59 | 1.8 | 2.07 | |
Water pressure drop (kPa) | 20 | 23 | 20 | 30 | 40 | 40 | 40 | 32 | 40 | 50 | |
Condensate pipe | DN20(Taper pipe external thread) |
Fan coil unit (3+1 row) | |||||||||||
Model number/ property | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-119 | FP-136 | FP-170 | EP-204 | FP-238 | |
Air Flow (m³/h) | Top grade | 340 | 510 | 680 | 850 | 1020 | 1190 | 1360 | 1700 | 2040 | 2380 |
Mid-rang | 255 | 383 | 510 | 638 | 765 | 893 | 1020 | 1275 | 1530 | 1785 | |
Low-end | 170 | 255 | 340 | 425 | 510 | 595 | 680 | 850 | 1020 | 1190 | |
Cooling(W) | Topgrade | 1800 | 2700 | 3600 | 4500 | 5400 | 6300 | 7200 | 9000 | 10800 | 12600 |
Mid-rang | 1440 | 2160 | 2880 | 3600 | 4320 | 5040 | 5760 | 7200 | 8640 | 10080 | |
Low-end | 1170 | 1755 | 2340 | 2925 | 3510 | 4095 | 4680 | 5850 | 7020 | 8190 | |
Energy efficiency coefficient of cooling (FCEER) W/W | 12Pa | 46 | 49 | 54 | 54 | 51 | 49 | 49 | 53 | 51 | 48 |
30Pa | 39 | 43 | 47 | 49 | 45 | 46 | 43 | 47 | 46 | 44 | |
50Pa | 35 | 39 | 41 | 43 | 42 | 43 | 38 | 40 | 40 | 38 | |
Heat supply (W) Water supply temperature 60°℃ | Top grade | 1210 | 1820 | 2430 | 3030 | 3650 | 4250 | 4860 | 6070 | 7290 | 8500 |
Mid-range | 1004 | 1565 | 1871 | 2333 | 2884 | 3315 | 3791 | 4492 | 5832 | 6630 | |
Low-end | 835 | 1256 | 1458 | 1757 | 2081 | 2423 | 2819 | 3460 | 4301 | 4590 | |
Energy efficiency (FCOOP) Water suppy temperature 60℃ | 12Pa | 33 | 35 | 39 | 39 | 37 | 36 | 36 | 39 | 38 | 36 |
30Pa | 27 | 31 | 34 | 35 | 33 | 34 | 31 | 34 | 34 | 33 | |
50Pa | 25 | 28 | 29 | 30 | 31 | 31 | 28 | 29 | 29 | 28 | |
Heat supply(W) Water supply temperature 45 ℃ | Top grade | 810 | 1210 | 1620 | 2020 | 2430 | 2830 | 3240 | 4050 | 4860 | 5670 |
Mid-range | 672 | 1041 | 1247 | 1555 | 1920 | 2207 | 2527 | 2997 | 3888 | 4423 | |
Low-end | 559 | 835 | 972 | 1172 | 1385 | 1613 | 1879 | 2309 | 2867 | 3062 | |
Energy efficiency coefficient of heating (FCCOP)W/W Water supply temperature 45 ° C | 12Pa | 22 | 23 | 26 | 26 | 25 | 24 | 23 | 26 | 25 | 24 |
30Pa | 18 | 20 | 22 | 23 | 22 | 22 | 20 | 23 | 22 | 22 | |
50Pa | 16 | 18 | 19 | 20 | 20 | 20 | 18 | 19 | 19 | 18 | |
Input power (W) | 12Pa | 36 | 50 | 60 | 74 | 93 | 112 | 130 | 147 | 183 | 221 |
30Pa | 43 | 57 | 70 | 84 | 105 | 121 | 151 | 169 | 206 | 245 | |
50Pa | 48 | 64 | 81 | 97 | 114 | 131 | 169 | 204 | 243 | 291 | |
Noise dB(A) | 12Pa | 37 | 39 | 41 | 43 | 45 | 46 | 46 | 48 | 50 | 52 |
30Pa | 40 | 42 | 44 | 46 | 47 | 48 | 48 | 50 | 52 | 54 | |
50Pa | 42 | 44 | 46 | 47 | 49 | 50 | 50 | 52 | 54 | 56 | |
Airblower | Form | Forward multi-wing centrifugal double suction fan | |||||||||
Quantity | 1 | 2 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | |
Electric machine | Form | Capacitor running asynchronous motor (220v/50Hz,protection class IP20,insulation class B) | |||||||||
Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | |
Heat exchanger | Structural form | Copper tube string aluminum sheet,mechanical expansion | |||||||||
Inlet and outlet diameter | RC3/4(Conical internal thread) | ||||||||||
Other | Design pressure 1.6MPa,test pressure 2.5MPa | ||||||||||
Cold water quantity (T/h) | 0.39 | 0.55 | 0.7 | 0.82 | 0.91 | 1.21 | 1.34 | 1.59 | 1.8 | 2.07 | |
Water pressure drop (kPa) | 20 | 23 | 20 | 30 | 40 | 40 | 40 | 32 | 40 | 50 | |
Condensate pipe | DN20(Taper pipe external thread) |
Video
FAQ
A: What's the reason for the excessive noise? How to solve it?
Q: Bearing damage, collision of blades with volute and gas accumulation in the pipeline.
Solution: Replace the bearing/motor, adjust the hoisting balance, and empty the air in the pipeline.
A: What's the reason for the poor drainage of condensed water? How to solve it?
Q: The pipeline slope is insufficient or blocked, and the equipment is inclined.
Solution: Clean the foreign bodies in the pipeline and adjust the installation angle to ensure that the drainage slope is ≥1%.
Core structure
Fan: low-noise centrifugal fan, equipped with capacitor motor, supports three-speed regulation.
Coil: The copper tube and aluminum fins form a heat exchanger, with the outer diameter of the copper tube of 10-16mm and the spacing between the fins of 2-3mm. The heat exchange efficiency is improved through optimized design.
Shell: galvanized steel plate or aluminum alloy material, corrosion-resistant and high strength, condensate pan adopts integrated molding process, no weld, good leakage resistance.
Control system: adjust the opening and closing of the electric valve and the speed of the fan through the thermostat, and control the water flow or air volume to achieve constant temperature.
Working principle
The unit forcibly circulates indoor air through the fan to make it flow over the surface of the coil. The cold/hot water flowing in the coil exchanges heat with the air, and then the air is cooled or heated and sent back to the room. Fresh air is supplemented after being treated by an independent fresh air system to ensure indoor air quality.
Product advantage
Concealed and beautiful: embedded in the ceiling, integrated with interior decoration, saving space and not affecting visual effects.
Low-noise operation: Low-noise fan and optimized air duct design are adopted, and the operation noise is as low as 40-50dB(A), which is suitable for the environment with high mute demand.
Energy saving and high efficiency: equipped with efficient heat exchanger and frequency conversion technology, the output of cold and heat can be adjusted to reduce energy consumption; Some models support four-pipe system, which can provide cooling/heating at the same time.
Uniform air supply: the design of three-dimensional spiral blades ensures uniform air distribution and avoids local temperature difference.Convenient maintenance: modular design and reserved access port are convenient for cleaning the filter screen and maintaining the fan and coil.
Flexible installation: the compact fuselage adapts to a variety of building structures, and the pipeline connection is simple, and the installation can be completed by one person.
Application scenarios
Commercial places: hotel rooms, shopping malls, office buildings, to meet the temperature control needs of independent spaces.
Medical environment: the hospital ward provides a clean and temperature-controlled rehabilitation environment.
Living space: family bedroom, villa, to achieve personalized temperature control and maintain indoor beauty.
Public facilities: exhibition hall, school, to meet the needs of large space air conditioning.
Regularly clean the filter and condenser to maintain airflow efficiency.
Regularly check the motor for safe and smooth operation.
Fan Coil Unit(3row) | |||||||||||
Model number/ property | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-119 | FP-136 | FP-170 | FP-204 | FP-238 | |
Air Flow (m³/h) | Top grade | 340 | 510 | 680 | 850 | 1020 | 1190 | 1360 | 1700 | 2040 | 2380 |
Mid-range | 255 | 383 | 510 | 638 | 765 | 893 | 1020 | 1275 | 1530 | 1785 | |
Low-end | 170 | 255 | 340 | 425 | 510 | 595 | 680 | 850 | 1020 | 1190 | |
Cooling(W) | Top grade | 1800 | 2700 | 3600 | 4500 | 5400 | 6300 | 7200 | 9000 | 10800 | 12600 |
Mid-range | 1440 | 2160 | 2880 | 3600 | 4320 | 5040 | 5760 | 7200 | 8640 | 10080 | |
Low-end | 1170 | 1755 | 2340 | 2925 | 3510 | 4095 | 4680 | 5850 | 7020 | 8190 | |
Energy efficieng coefficient of cooling (FCEER) W/W | 12Pa | 46 | 49 | 54 | 54 | 51 | 49 | 49 | 53 | 51 | 48 |
30Pa | 39 | 43 | 47 | 49 | 45 | 46 | 43 | 47 | 46 | 44 | |
50Pa | 35 | 39 | 41 | 43 | 42 | 43 | 38 | 40 | 40 | 38 | |
Heat supply(W) Water supply temperature 60℃ | Top grade | 2700 | 4050 | 5400 | 6750 | 8100 | 9450 | 10800 | 13500 | 16200 | 18900 |
Mid-range | 2160 | 3240 | 4320 | 5400 | 6480 | 7560 | 8640 | 10800 | 12960 | 15120 | |
Low-end | 1755 | 2633 | 3510 | 4388 | 5265 | 6143 | 7020 | 8775 | 10530 | 12285 | |
Energy efficieng coefficient of heatig (FCCOP) W/W Water supply temperature 60℃ | 12Pa | 68 | 73 | 81 | 82 | 76 | 74 | 73 | 79 | 77 | 72 |
30Pa | 58 | 65 | 70 | 73 | 68 | 69 | 64 | 70 | 69 | 66 | |
50Pa | 53 | 59 | 61 | 64 | 63 | 64 | 58 | 60 | 60 | 57 | |
Heat supply (W) Water supply temperature 45℃ | Top grade | 1800 | 2700 | 3600 | 4500 | 5400 | 6300 | 7200 | 9000 | 10800 | 12600 |
Mid-range | 1440 | 2160 | 2880 | 3600 | 4320 | 5040 | 5760 | 7200 | 8640 | 10080 | |
Low-end | 1170 | 1755 | 2340 | 2925 | 3510 | 4095 | 4680 | 5850 | 7020 | 8190 | |
Energy efficieng coefficient of heatig (FCCOP) W/W Water supply temperature 45℃ | 12Pa | 46 | 49 | 54 | 54 | 51 | 49 | 49 | 53 | 51 | 48 |
30Pa | 39 | 43 | 47 | 49 | 45 | 46 | 43 | 47 | 46 | 44 | |
50Pa | 35 | 39 | 41 | 43 | 42 | 43 | 38 | 40 | 40 | 38 | |
Input power(W) | 12Pa | 36 | 50 | 60 | 74 | 93 | 112 | 130 | 147 | 183 | 221 |
30Pa | 43 | 57 | 70 | 84 | 105 | 121 | 151 | 169 | 206 | 245 | |
50Pa | 48 | 64 | 81 | 97 | 114 | 131 | 169 | 204 | 243 | 291 | |
Noise dB(A) | 12Pa | 37 | 39 | 41 | 43 | 45 | 46 | 46 | 48 | 50 | 52 |
30Pa | 40 | 42 | 44 | 46 | 47 | 48 | 48 | 50 | 52 | 54 | |
50Pa | 42 | 44 | 46 | 47 | 49 | 50 | 50 | 52 | 54 | 56 | |
Air blower | Form | Forward multi-wing centrifugal double suction fan | |||||||||
Quantity | 1 | 2 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | |
Electric machine | Form | Capacitor running asynchronous motor(220V/50Hz,protection class IP20,insulation class B) | |||||||||
Quantity | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | |||
Heat exchanger | Structuralform | Copper tube string aluminum sheet,mechanical expansion | |||||||||
Inlet and outet diameter | RC3/4(Conical internal thread) | ||||||||||
Other | Design pressure 1.6MPa,test pressure 2.5MPa | ||||||||||
Cold water quantity (T/h) | 0.39 | 0.55 | 0.7 | 0.82 | 0.91 | 1.21 | 1.34 | 1.59 | 1.8 | 2.07 | |
Water pressure drop (kPa) | 20 | 23 | 20 | 30 | 40 | 40 | 40 | 32 | 40 | 50 | |
Condensate pipe | DN20(Taper pipe external thread) |
Fan coil unit (3+1 row) | |||||||||||
Model number/ property | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-119 | FP-136 | FP-170 | EP-204 | FP-238 | |
Air Flow (m³/h) | Top grade | 340 | 510 | 680 | 850 | 1020 | 1190 | 1360 | 1700 | 2040 | 2380 |
Mid-rang | 255 | 383 | 510 | 638 | 765 | 893 | 1020 | 1275 | 1530 | 1785 | |
Low-end | 170 | 255 | 340 | 425 | 510 | 595 | 680 | 850 | 1020 | 1190 | |
Cooling(W) | Topgrade | 1800 | 2700 | 3600 | 4500 | 5400 | 6300 | 7200 | 9000 | 10800 | 12600 |
Mid-rang | 1440 | 2160 | 2880 | 3600 | 4320 | 5040 | 5760 | 7200 | 8640 | 10080 | |
Low-end | 1170 | 1755 | 2340 | 2925 | 3510 | 4095 | 4680 | 5850 | 7020 | 8190 | |
Energy efficiency coefficient of cooling (FCEER) W/W | 12Pa | 46 | 49 | 54 | 54 | 51 | 49 | 49 | 53 | 51 | 48 |
30Pa | 39 | 43 | 47 | 49 | 45 | 46 | 43 | 47 | 46 | 44 | |
50Pa | 35 | 39 | 41 | 43 | 42 | 43 | 38 | 40 | 40 | 38 | |
Heat supply (W) Water supply temperature 60°℃ | Top grade | 1210 | 1820 | 2430 | 3030 | 3650 | 4250 | 4860 | 6070 | 7290 | 8500 |
Mid-range | 1004 | 1565 | 1871 | 2333 | 2884 | 3315 | 3791 | 4492 | 5832 | 6630 | |
Low-end | 835 | 1256 | 1458 | 1757 | 2081 | 2423 | 2819 | 3460 | 4301 | 4590 | |
Energy efficiency (FCOOP) Water suppy temperature 60℃ | 12Pa | 33 | 35 | 39 | 39 | 37 | 36 | 36 | 39 | 38 | 36 |
30Pa | 27 | 31 | 34 | 35 | 33 | 34 | 31 | 34 | 34 | 33 | |
50Pa | 25 | 28 | 29 | 30 | 31 | 31 | 28 | 29 | 29 | 28 | |
Heat supply(W) Water supply temperature 45 ℃ | Top grade | 810 | 1210 | 1620 | 2020 | 2430 | 2830 | 3240 | 4050 | 4860 | 5670 |
Mid-range | 672 | 1041 | 1247 | 1555 | 1920 | 2207 | 2527 | 2997 | 3888 | 4423 | |
Low-end | 559 | 835 | 972 | 1172 | 1385 | 1613 | 1879 | 2309 | 2867 | 3062 | |
Energy efficiency coefficient of heating (FCCOP)W/W Water supply temperature 45 ° C | 12Pa | 22 | 23 | 26 | 26 | 25 | 24 | 23 | 26 | 25 | 24 |
30Pa | 18 | 20 | 22 | 23 | 22 | 22 | 20 | 23 | 22 | 22 | |
50Pa | 16 | 18 | 19 | 20 | 20 | 20 | 18 | 19 | 19 | 18 | |
Input power (W) | 12Pa | 36 | 50 | 60 | 74 | 93 | 112 | 130 | 147 | 183 | 221 |
30Pa | 43 | 57 | 70 | 84 | 105 | 121 | 151 | 169 | 206 | 245 | |
50Pa | 48 | 64 | 81 | 97 | 114 | 131 | 169 | 204 | 243 | 291 | |
Noise dB(A) | 12Pa | 37 | 39 | 41 | 43 | 45 | 46 | 46 | 48 | 50 | 52 |
30Pa | 40 | 42 | 44 | 46 | 47 | 48 | 48 | 50 | 52 | 54 | |
50Pa | 42 | 44 | 46 | 47 | 49 | 50 | 50 | 52 | 54 | 56 | |
Airblower | Form | Forward multi-wing centrifugal double suction fan | |||||||||
Quantity | 1 | 2 | 2 | 2 | 2 | 2 | 3 | 4 | 4 | 4 | |
Electric machine | Form | Capacitor running asynchronous motor (220v/50Hz,protection class IP20,insulation class B) | |||||||||
Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | |
Heat exchanger | Structural form | Copper tube string aluminum sheet,mechanical expansion | |||||||||
Inlet and outlet diameter | RC3/4(Conical internal thread) | ||||||||||
Other | Design pressure 1.6MPa,test pressure 2.5MPa | ||||||||||
Cold water quantity (T/h) | 0.39 | 0.55 | 0.7 | 0.82 | 0.91 | 1.21 | 1.34 | 1.59 | 1.8 | 2.07 | |
Water pressure drop (kPa) | 20 | 23 | 20 | 30 | 40 | 40 | 40 | 32 | 40 | 50 | |
Condensate pipe | DN20(Taper pipe external thread) |
A: What's the reason for the excessive noise? How to solve it?
Q: Bearing damage, collision of blades with volute and gas accumulation in the pipeline.
Solution: Replace the bearing/motor, adjust the hoisting balance, and empty the air in the pipeline.
A: What's the reason for the poor drainage of condensed water? How to solve it?
Q: The pipeline slope is insufficient or blocked, and the equipment is inclined.
Solution: Clean the foreign bodies in the pipeline and adjust the installation angle to ensure that the drainage slope is ≥1%.