Horizontal fan coil is the terminal equipment of central air conditioning system, which is composed of small fan, motor, heat exchange coil, casing, etc. It is usually hidden in the ceiling, and only the air outlet, air return outlet and maintenance port are reserved. It realizes indoor temperature adjustment by exchanging heat between chilled water or hot water and air, and has the functions of refrigeration, heating and dehumidification. This equipment is widely used in hotels, hotels, hospitals, office buildings and other places, especially suitable for scenes that need concealed installation and require high indoor aesthetics.
  • VOLKS

Model:
Availability:
Quantity:

Product Features

Core structure

  • Fan: low-noise centrifugal fan, equipped with capacitor motor, supports three-speed regulation.

  • Coil: The copper tube and aluminum fins form a heat exchanger, with the outer diameter of the copper tube of 10-16mm and the spacing between the fins of 2-3mm. The heat exchange efficiency is improved through optimized design.

  • Shell: galvanized steel plate or aluminum alloy material, corrosion-resistant and high strength, condensate pan adopts integrated molding process, no weld, good leakage resistance.

  • Control system: adjust the opening and closing of the electric valve and the speed of the fan through the thermostat, and control the water flow or air volume to achieve constant temperature.

Working principle

  • The unit forcibly circulates indoor air through the fan to make it flow over the surface of the coil. The cold/hot water flowing in the coil exchanges heat with the air, and then the air is cooled or heated and sent back to the room. Fresh air is supplemented after being treated by an independent fresh air system to ensure indoor air quality.

Product advantages and Application scenarios

Product advantage

  • Concealed and beautiful: embedded in the ceiling, integrated with interior decoration, saving space and not affecting visual effects.

  • Low-noise operation: Low-noise fan and optimized air duct design are adopted, and the operation noise is as low as 40-50dB(A), which is suitable for the environment with high mute demand.

  • Energy saving and high efficiency: equipped with efficient heat exchanger and frequency conversion technology, the output of cold and heat can be adjusted to reduce energy consumption; Some models support four-pipe system, which can provide cooling/heating at the same time.

  • Uniform air supply: the design of three-dimensional spiral blades ensures uniform air distribution and avoids local temperature difference.Convenient maintenance: modular design and reserved access port are convenient for cleaning the filter screen and maintaining the fan and coil.

  • Flexible installation: the compact fuselage adapts to a variety of building structures, and the pipeline connection is simple, and the installation can be completed by one person.

Application scenarios

  • Commercial places: hotel rooms, shopping malls, office buildings, to meet the temperature control needs of independent spaces.

  • Medical environment: the hospital ward provides a clean and temperature-controlled rehabilitation environment.

  • Living space: family bedroom, villa, to achieve personalized temperature control and maintain indoor beauty.

  • Public facilities: exhibition hall, school, to meet the needs of large space air conditioning.

Equipment Maintenance and Care

Regularly clean the filter and condenser to maintain airflow efficiency.

Regularly check the motor for safe and smooth operation.

Fan Coil Unit(3row)
Model number/
property
FP-34FP-51FP-68FP-85FP-102FP-119FP-136FP-170FP-204FP-238
Air Flow
(m³/h)
Top grade340510680850102011901360170020402380
Mid-range2553835106387658931020127515301785
Low-end17025534042551059568085010201190
Cooling(W)Top grade180027003600450054006300720090001080012600
Mid-range14402160288036004320504057607200864010080
Low-end1170175523402925351040954680585070208190
Energy efficieng
coefficient of cooling
   (FCEER)
    W/W
12Pa46495454514949535148
30Pa39434749454643474644
50Pa35394143424338404038
Heat supply(W)
Water supply
temperature 60℃
Top grade27004050540067508100945010800135001620018900
Mid-range2160324043205400648075608640108001296015120
Low-end175526333510438852656143702087751053012285
Energy efficieng
coefficient of heatig
   (FCCOP)
    W/W
Water supply
temperature 60℃
12Pa68738182767473797772
30Pa58657073686964706966
50Pa53596164636458606057
Heat supply (W)
Water supply
temperature 45℃
Top grade180027003600450054006300720090001080012600
Mid-range14402160288036004320504057607200864010080
Low-end1170175523402925351040954680585070208190
Energy efficieng
coefficient of heatig
   (FCCOP)
    W/W
Water supply
temperature 45℃
12Pa46495454514949535148
30Pa39434749454643474644
50Pa35394143424338404038
Input power(W)12Pa3650607493112130147183221
30Pa43577084105121151169206245
50Pa48648197114131169204243291
Noise
dB(A)
12Pa37394143454646485052
30Pa40424446474848505254
50Pa42444647495050525456
Air blowerFormForward multi-wing centrifugal double suction fan
Quantity1222223444
Electric
machine
FormCapacitor running asynchronous motor(220V/50Hz,protection class IP20,insulation class B)
Quantity1

1112222
Heat exchangerStructuralform
Copper tube string aluminum sheet,mechanical expansion
Inlet and outet diameter
RC3/4(Conical internal thread)
Other
Design pressure 1.6MPa,test pressure 2.5MPa
Cold water quantity (T/h)0.390.550.70.820.911.211.341.591.82.07
Water pressure drop (kPa)20232030404040324050
Condensate pipeDN20(Taper pipe external thread)
Fan coil unit (3+1 row)
Model number/
property
FP-34FP-51FP-68FP-85FP-102FP-119FP-136FP-170EP-204FP-238
Air Flow
(m³/h)
Top grade340510680850102011901360170020402380
Mid-rang2553835106387658931020127515301785
Low-end17025534042551059568085010201190
Cooling(W)Topgrade180027003600450054006300720090001080012600
Mid-rang14402160288036004320504057607200864010080
Low-end1170175523402925351040954680585070208190
Energy efficiency
coefficient of cooling
   (FCEER)
    W/W
12Pa46495454514949535148
30Pa39434749454643474644
50Pa35394143424338404038
Heat supply (W)
Water supply
temperature 60°℃
Top grade1210182024303030365042504860607072908500
Mid-range1004156518712333288433153791449258326630
Low-end835125614581757208124232819346043014590
Energy efficiency
 (FCOOP)
Water suppy temperature 60℃
12Pa33353939373636393836
30Pa27313435333431343433
50Pa25282930313128292928
Heat supply(W)
Water supply
temperature 45 ℃
Top grade810121016202020243028303240405048605670
Mid-range672104112471555192022072527299738884423
Low-end5598359721172138516131879230928673062
Energy efficiency coefficient of heating
(FCCOP)W/W
Water supply temperature 45 ° C
12Pa22232626252423262524
30Pa18202223222220232222
50Pa16181920202018191918
Input power
(W)
12Pa3650607493112130147183221
30Pa43577084105121151169206245
50Pa48648197114131169204243291
Noise
dB(A)
12Pa37394143454646485052
30Pa40424446474848505254
50Pa42444647495050525456
AirblowerFormForward multi-wing centrifugal double suction fan
Quantity1222223444
Electric
machine
FormCapacitor running asynchronous motor (220v/50Hz,protection class IP20,insulation class B)
Quantity1111112222
Heat exchangerStructural formCopper tube string aluminum sheet,mechanical expansion
Inlet and outlet diameterRC3/4(Conical internal thread)
OtherDesign pressure 1.6MPa,test pressure 2.5MPa
Cold water quantity (T/h)0.390.550.70.820.911.211.341.591.82.07
Water pressure drop (kPa)20232030404040324050
Condensate pipeDN20(Taper pipe external thread)


Video


FAQ

A: What's the reason for the excessive noise? How to solve it?

Q: Bearing damage, collision of blades with volute and gas accumulation in the pipeline. 

Solution: Replace the bearing/motor, adjust the hoisting balance, and empty the air in the pipeline.


A: What's the reason for the poor drainage of condensed water? How to solve it?

Q: The pipeline slope is insufficient or blocked, and the equipment is inclined. 

Solution: Clean the foreign bodies in the pipeline and adjust the installation angle to ensure that the drainage slope is ≥1%.

Quick Links

Product Category

About VOLKS

Resources

Contact Us

 Email: james@sdvolksgroup.com
 Tel: +86-18315978656
 WhatsApp: +8613310606210
Address: East Tianqu Road, Zhongao Street, Economic and Technological Development Zone, Dezhou city, Shandong province, China. 253000
Copyright © 2024 Shandong VOLKS Air Conditioning Group Co., Ltd. All Rights Reserved. Sitemap. Privacy Policy.